| CABLE
LADDERS ELECTROLINK CABLE LADDERS ARE FABRICATED WITH THE FOLLOWING SPECIFICATION: MEDIUM DUTY WITH OUTSIDE FLANGE AND HEAVY DUTY WITH OUTSIDE RETURNED UPPER FLANGEFOR EXTRA RIGIDITY AND STANDARD LENGTHS ARE 2.44 AND 3.0 METERS. LENGTHS OF 3.658 METERS (12FT.) AND 7.315 METERS (24 FT.) ARE AVAILABLE ON REQUEST. STANDARD FINISHES ARE MILL GALVANIZED TO ASTM 525 - G90 (BS2989) AND HOT DIP GALVANIZED AFTER FABRICATION TO ASTM A123 (BS729). RUNGS ARE EITHER RIVETTED TYPE (FOR LIGHT DUTY LD SERIES), WELDED TO SIDE MEMBER TYPE (FOR MEDIUM AND HEAVY DUTY MU AND HS SERIES) OR THE SWAGED ROUND TUBULER RUNGS TYPE (FOR HEAVY DUTY AM SERIES). OPTIONAL MATERIALS AND FINISHES ARE ALSO AVAILABLE TO SUIT COSTUMER'S REQUIREMENT. |
| AM - SERIES |
|
EXTRA HEAVY DUTY CABLE LADDER WITH SWAGED ROUND TUBULAR TYPE RUNGS FLATTENED ON TOP FOR WIDER CABLE BEARING SURFACE, KNOWN FOR ITS RIGIDITY AND SUPERB LOAD CARRYING CAPACITY. |
|
|
WIDTH
: FROM 150 TO 900mm |
STANDARD
MATERIALS/FINISHES MILL GALVANIZED (M.G.) TO ASTM 525-G90 (BS2989) HOT DIP GALVANIZED AFTER FABRICATION (HDGAF) TO ASTM A123 (BS729) ALUMINUM - 6063 - T6 |
|
NON
STANDARD FINISH : |
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
WORKING LOAD CAPACITY |
Aluminum
|
|||||||||
|
NEMA
CLASS DESIGNATION |
SIDE
HEIGHT mm |
THICK mm
|
1.8M (6')
WT DEF |
2.4M (8')
WT DEF |
3.0M (10')
WT DEF |
3.6 (12')
WT DEF |
4.2M (14')
WT DEF |
4.8M (16') 5 5 M(16')
WT DEF
|
5 5 M(16')
WT DEF
|
6.0 M(20')
WT DEF
|
|
8A |
100 |
1.20 |
432-5.8 |
242-10.6 |
152-16.0 |
102-22.6 |
||||
|
TO |
125 |
1.2 |
566-4.5 |
310-7.8 |
187-11.7 |
85-15.7 |
||||
|
8C |
150 |
1.50 |
528-2.8 |
289-4.6 |
176-71 |
116-9.6 |
||||
|
175 |
1.5 |
621.23 |
336-4.0 |
206-5.6 |
136-7.6 |
|||||
|
12A |
100 |
1.5 |
432-5.8 |
432-5.6 |
152-16.0 |
136-7.6 |
||||
|
TO |
125 |
1.5 |
566-4.5 |
566-4.5 |
187-11.7 |
102-22.6 |
||||
|
12C |
150 |
1.5 |
680-2.7 |
660-2.7 |
227-7.3 |
85-15.7 |
||||
|
175 |
1.5 |
1006-3.0 |
485-4.8 |
269-6.6 |
152-10.1 |
|||||
|
16A |
100 |
1.5 |
429-13.4 |
269-20.5 |
158-7.8 |
|||||
|
TO |
125 |
1.5 |
565-10.7 |
3.6-16.7 |
186-29.7 |
125-36.8 |
96-48.5 |
|||
|
16C |
150 |
1.5 |
630.7.8 |
383-11.6 |
251-23.8 |
168-29.9 |
127-39.0 |
|||
|
175 |
1.5 |
745-6.3 |
452-9.3 |
253-15.7 |
176-20.5 |
127-25.3 |
||||
|
20A |
100 |
1.5 |
298-12.9 |
207-16.5 |
149-20.3 |
|||||
|
TO |
125 |
1.5 |
2150-32.2 |
170-40.3 |
130-52.8 |
99-64.0 |
77-75.6 |
|||
|
20C |
150 |
2 |
275-22.6 |
198-29.9 |
148-38.3 |
106-44.4 |
78-49.2 |
|||
|
175 |
2 |
438-20.0 |
294-24.8 |
224-32.5 |
170-393 |
155-48.5 |
||||
|
560-16.7 |
368-20.3 |
282-26.6 |
196-29.7 |
150-34.7 |
||||||
|
WORKING LOAD CAPACITY |
Steel
|
|||||||||
|
NEMA
CLASS
DESIGNATION
|
SIDE
HEIGHT mm
|
THICK mm
|
1.8M (6')
WT DEF
|
2.4M (8')
WT DEF
|
3.0M (10')
WT DEF
|
3.6 (12')
WT DEF
|
4.2M (14')
WT DEF
|
4.8M (16') 5 5 M(16')
WT DEF
|
5 5 M(16')
WT DEF
|
6.0 M(20')
WT DEF
|
|
8A |
100 |
268-8.6 |
151-15.24 |
96-23.8 |
67-23.8 |
|||||
|
TO |
125 |
479-8.3 |
269-14.9 |
173-22.1 |
114.32 |
|||||
|
8C |
150 |
531-5.5 |
282-9.4 |
170-13.9 |
111-18.8 |
|||||
|
175 |
615-4.5 |
327-7.8 |
197-11.6 |
129-15.7 |
||||||
|
12A |
100 |
329-8.8 |
185-16.0 |
118-25.1 |
81-36.0 |
|||||
|
TO |
125 |
479-8.3 |
269-14.9 |
173-22.1 |
114-32 |
|||||
|
12C |
150 |
531-5.5 |
282-9.4 |
170-13.9 |
111-18.8 |
|||||
|
175 |
799-4.3 |
423-7.3 |
254-10.9 |
164-14.4 |
||||||
|
16A |
100 |
371-17.5 |
238-1.6 |
165-2.3 |
75-57.4 |
37-69.8 |
||||
|
TO |
125 |
384-11.1 |
245-17.5 |
142-20.8 |
75-34.5 |
41.4-46.4 |
||||
|
16C |
150 |
562-12.4 |
328-17.5 |
227-25.4 |
115-40.9 |
74-63.7 |
||||
|
175 |
802-11.1 |
470-15.7 |
327-22.8 |
176-38.8 |
112-60.7 |
|||||
|
20A |
100 |
224-40.9 |
121-69.6 |
76.9-108.4 |
||||||
|
TO |
125 |
229-38.3 |
116-46.9 |
75-73.4 |
||||||
|
20C |
150 |
318-23.3 |
179-41.4 |
113-64.7 |
||||||
|
175 |
463-23.6 |
260-42.1 |
167-65.7 |
|||||||
| 1) | Evenly distributed (kg / m), span in meters (ft), simply beam, safety factor: 1.5 (to convert safety factor to 2.0, multiply wt-defl. by .75). |
| 2) | While every endeavour has been made to ensure the accuracy of this figures, results are based on average test results and are therefore not a warranty of the performance of electrolink cable trough. |
| 3) | Please consult factory for other sizes/dimensions and weights of AM series cable ladder. |